SISO Engineering has published a guide to behind-the-meter batteries for data centers, covering the four jobs a battery performs alongside gas turbines, how to size it, and why its value depends on controls that agree with the turbines.
-- SISO Engineering, a Houston-based gas turbine controls and analytics firm, has published a technical guide on the roles and limits of behind-the-meter batteries for data centers. The article explains why a battery energy storage system (BESS) has become the natural partner for gas turbines on islanded and grid-light facilities, and where that partnership breaks down. The full guide is available at https://siso-eng.com/behind-the-meter-batteries-for-data-centers/
The guide arrives as more developers build on-site generation to serve AI data centers, an approach SISO Engineering covers at https://siso-eng.com/engineering-consultant-services/behind-the-meter-data-center-power/ Many of those projects start as powered land, meaning sites with acreage, fuel access and a position on the grid, explained at https://siso-eng.com/engineering-consultant-services/powered-land/ AI load is the reason batteries matter on these sites. In a July 2025 white paper, the North American Electric Reliability Corporation (NERC) recorded a 50 MW block of a 200 MW AI training data center changing demand at 1.9 per unit per second for about 250 milliseconds. That is faster than rotating machinery can follow, and a BESS responds in a fraction of a second.
According to the guide, a battery on a data center facility typically carries four roles. Load smoothing absorbs fast load steps so turbine governors see a flatter demand. Bridging carries load between a disturbance and the moment another source is ready. Black start supplies the initial energy to restart generation with no outside power. Peak support covers short demand peaks, so the turbine fleet can be sized closer to average load. The roles compete for the same stored energy, and the guide recommends deciding in writing, before commissioning, which role takes priority at each state of charge.
Sizing follows from those roles. Power capacity, in megawatts, sets how large a step the battery can absorb. Energy capacity, in megawatt-hours, sets how long it can hold that output. The guide notes that a battery sized for smoothing is not automatically sized for black start.
The article is direct about what batteries cannot do. A facility running at hundreds of megawatts around the clock uses far more energy each day than any reasonable battery holds. “A BESS moves energy in time; it does not create it,” the SISO Engineering analysis states. On a behind-the-meter site, the generation fleet has to recharge the battery. Gas turbines, in turn, carry steady load well but follow fast repetitive steps poorly. The guide concludes that neither technology alone matches AI load, and the pairing works only when it is controlled as one plant. SISO Engineering describes that approach at https://siso-eng.com/engineering-consultant-services/hybrid-power-systems/
When that condition is not met, the guide lists four risks: two control systems responding to the same error, mismatched assumptions about ramp rates and response times, protection settings that trip each other, and state-of-charge drift that leaves the battery full or empty at the wrong moment. It recommends that every BESS specification state response time and ramp limits, setpoint authority, state-of-charge windows for each role, protection and ride-through behavior, and the data points exposed to plant control and monitoring.
The guide also sets out where responsibilities sit. Battery supply stays with the manufacturers, the OEMs commission their own equipment, and plant control and asset dispatch stay with the owner’s distributed control system (DCS) and energy management system (EMS). SISO Engineering’s SnapShot platform provides a single view of how the battery and turbines perform together, with details at https://siso-eng.com/products/snapshot/. As a proof point, the article cites SISO Engineering’s controls work on a battery-supported black start system at Sentinel Energy Center in Southern California, a utility-connected plant rather than a data center. The project received the ENR West 2024 Best Energy/Industrial Project award, and according to SISO Engineering, the system has been activated twice after utility disturbances.
About SISO Engineering: SISO Engineering is an independent gas turbine controls, automation, and analytics firm founded in 2018 and headquartered in Houston, Texas. Its SnapShot platform provides monitoring and analytics across mixed fleets of turbines, engines, and battery storage for power plants and AI data centers across North America, South America, and Europe. More information is available at https://siso-eng.com/about/
Contact Info:
Name: Kate Sias
Email: Send Email
Organization: SISO Engineering
Address: 802 Lovett Boulevard, Houston, Texas 77006, United States
Phone: +1-713-287-1896
Website: https://siso-eng.com
Source: NewsNetwork
Release ID: 89210382
If there are any errors, inconsistencies, or queries arising from the content contained within this press release that require attention or if you need assistance with a press release takedown, we kindly request that you inform us immediately by contacting [email protected] (it is important to note that this email is the authorized channel for such matters, sending multiple emails to multiple addresses does not necessarily help expedite your request). Our reliable team will be available to promptly respond within 8 hours, taking proactive measures to rectify any identified issues or providing guidance on the removal process. Ensuring accurate and dependable information is our top priority.